Generator
Efficiency
Normally, a generator is designed @ 0.85 Lag (inductive) and
should be operated at this region in any given MW.
If during low load of operations, always look for the power
factor of the generator and adjust accordingly to smooth out generator voltage
and operation costs.
Adjust the Generator voltage (increase or decrease) until it
satisfies the Generator power factor vs Generator Voltage and Grid Voltage
whilst looking at the Grid frequency. The idea is to always keep the reactive
power zero MVAR and adjust accordingly. Ideally a power factor of 1 is perfect but
impossible to achieve and operator should aim to control the generator at this
state.
See the Tap Position for the Corresponding Generator Voltage
GTG Unit # 1 / 2 / 3 / 4 / 5 / 7 / 9 (Have to check
Generator Voltage vs Tap Position)
Tap Position |
LV |
HV |
1 |
11 kV |
|
2 |
|
|
3 |
|
|
4 |
|
|
5 |
|
|
6 |
|
|
7 |
|
|
8 |
|
|
9 |
|
GTG Unit 11 (Have to check Generator Voltage vs Tap
Position)
Tap Position |
LV |
HV |
1 |
15 kV |
|
2 |
|
|
3 |
|
|
4 |
|
|
5 |
|
|
6 |
|
|
7 |
|
|
8 |
|
|
9 |
|
LOWER TAP |
Increase
reactive power (exporting) |
Increase
Generator Voltage |
|
HIGHER TAP |
Decrease reactive
power (importing) |
Decrease
Generator Voltage |
Operating a generator beyond the design of the Generator
will pose a problem within the generator and will eventually high operation
cost (Fuel Consumption). Protections are in place to protect the generator from
certain heating and to inform the operator for necessary adjustments as per
generator efficiency. See Generator capability curve for the limitations of the
generator operations.
Rotor Winding Heating – Beyond generator curve (OEL)
Stator Heating – Ideal
Core Winding Heating – Below generator curve (UEL)
Protection System:
·
Overexcitation Limiter (OEL) – Protects the
generator filed circuitry from excessive current versus time heating. Its
settings should be coordinated with the generator capability curve in the
overexcitation region. The setting should be also allowing the exciter to
respond to fault conditions where field current is boosted (field forcing) to a
high level for a short period of time. Typically, the OEL takes over control to
limit field current from the steady state AVR control for close in faults where
the induced field current remains high or during sustained system low voltage
conditions requiring field current above rated levels.
·
V/Hz Limiter – Limits the generator V/Hz ratio
by limiting the generator voltage to a programmed setting. Steady state limit is
+/- 5% of rated generator stator terminal voltage at rated frequency. The
setting should permit short time excursions during transient conditions. The
V/Hz limiter is a limit function to the AVR setpoint and is not a variable.
·
Field Overcurrent Protection – DC overcurrent
protection is provided in exciters. Some exciters have a protective inverse
time module that calculates the I*t to provide an inverse time curve. It needs
to be coordinated with the OEL settings as well as the short time capability of
the field. It also should allow field forcing to take place during fault
conditions. In some cases, this protection may trip the exciter if OEL
initiated runback is unsuccessful.
·
Under excitation Limit (UEL) – prevents the
generator from exceeding its core-end heating and/or its stability limit, when
it is operating at a leading power factor. It prevents the AVR from reducing
excitation to such a low level that the generator is in danger of losing
synchronism. Exceeding machine under-excited capability or tripping due to
exceeding the loss of excitation protection setting. The UEL must prevent
reduction of field current to a level where the generator loss-of-field
protection may operate.
No comments:
Post a Comment